Corda 30
IO-Link
The first peristaltic metering pump with native IO-Link.
Today's Corda is driven step by step from the controller, and nothing inside the pump knows about the pump. The IO-Link Corda has a controller of its own. It runs its motor, watches its sensors, enforces its own safety stops and reports all of it as data.

01 / Plug and produce
A metering pump that behaves like a sensor
One cable and no analog scaling. The pump shows up on your IO-Link master like any other device on it.

01
Plug in one M12 cable
A standard A-coded IO-Link cable from any port. It carries the data and the 24 V that runs the pump's own controller.
02
Set flow in mL/min
The pump holds its own calibration and turns flow into rotor speed itself. 0.01 mL/min resolution at any turndown, with no 4-20 mA scaling.
03
Read what happened
Flow delivered, motor torque and eight status bits every cycle; events for every stop; counters for tube life and running hours.
04
Swap without setup
IO-Link Data Storage keeps the pump's settings and calibration in the port. A replacement pump gets them back when it's plugged in.
02 / Architecture
Logic on the link, power on its own
The pump's controller runs from the IO-Link port. The servo has its own 48 V supply inside the pump. With mains off, the pump stays on the link and reports no motor power instead of disappearing.
IO-Link master
Cortex 7 IO-Link card
On the 6PSevo
Any IO-Link master
Through the pump's IODD
M12 · L+ · C/Q · L−
Corda 30 IO-Link
Pump controller
IO-Link device · runs on the port's 24 V
Sensors
Cover · liquid in head · enclosure air
Servo motor
Speed out · torque back
48 V motor supply
From mains, measured by the controller
03 / Safety in the pump
Its own stops, in its own firmware
These stops hold with the link down or the controller misconfigured.

Nothing restarts by itself. After a stop, the pump runs again only on the controller's Reset fault, once the cause has gone. Closing the cover never starts it: a guard closing must not start a machine (ISO 14119).
01
Cover open
A sensor on the front cover. With the cover off, the pump stops, whatever the controller asks.
02
Liquid in the pump head
An optical prism sensor in the head's drain sees a split tube. Optical, so it also sees liquids that conduct too poorly for a conductive probe, such as neat polymer.
03
Stall
Torque from the servo, averaged and timed: the same stall rule the 6PSevo uses today. Set it to stop the pump or to report only.
04
Link lost
If the master's messages stop, or it marks the outputs invalid, the pump stops. Only a new Run from the controller starts it again.
04 / On the wire
Process data, settings and events
From the draft IODD. Details may change before release.
Process data in
pump to controller · 10 octets| Value | Size | Note |
|---|---|---|
| Flow being delivered | 32 bit | 0.01 mL/min |
| Motor torque | 16 bit | 0.1 %, from the servo's HLFB |
| Running | bit | |
| Cover open | bit | The pump has stopped |
| Liquid in pump head | bit | The pump has stopped |
| Stall | bit | |
| Motor fault | bit | |
| No motor power | bit | Reported as such, not as a stall |
| Tube change due | bit | From the tube-life setting |
| Setpoint limited | bit | Asked for more than the maximum speed |
Process data out
controller to pump · 5 octets| Value | Size | Note |
|---|---|---|
| Flow setpoint | 32 bit | 0.01 mL/min, 0 to 500 mL/min |
| Run | bit | |
| Reset fault | bit | On its rising edge |
Communication
| Item | Value |
|---|---|
| Connector | M12, A-coded, 4-pin |
| Transmission rate | COM3, 230.4 kbit/s |
| Minimum cycle time | 2 ms |
| Process data | 10 octets in, 5 octets out |
| Description | IODD (IO-Link 1.1) |
| Logic power | From the port's L+, 24 V |
Settings
ISDU| Setting | Value |
|---|---|
| Calibration | mL per revolution of the head (nominally 8.333) |
| Maximum speed | In 0.1 RPM, 60 RPM at most |
| Stall action | Report only, or stop |
| Tube life | Revolutions, for a tube-change reminder |
Counters and readings
- Revolutions since the tube was changed
- Total revolutions
- Running hours
- Motor supply voltage
- Tube changed system command resets the tube's count
Events
- Cover openError
- Liquid in pump headError
- Motor stallError
- Motor faultError
- No motor powerError
- Tube change dueWarning
Firmware updates
Updated over the same cable
New pump firmware goes in over IO-Link, signed and checked before it runs. No laptop at the pump and no opening the enclosure.
With Cortex 7
First on the 6PSevo
The Cortex 7 controller's IO-Link card brings the pump's events into its alarms, and its counters onto the maintenance screen. Any IO-Link master can read the pump through its IODD.
Be first on IO-Link.